  • For connection to Schrader valves
  • No frostbitten or burned hands
  • 99 % less refrigerant loss
  • Connection in seconds
  • No hand tightening required
Video
  • WEH® TW111 | Instant connection to HVAC-R service ports
    WEH® TW111 | Instant connection to HVAC-R service ports
    The quick release couplers with their distinctive blue and red colour coding for the low and high pressure side of AC systems are the ideal tool for filling / charging of refrigerants (R134a). They connect instantly to the Schrader SAE 1/4" service port and are available as straight or 90° elbow couplings. When disconnecting hazardous discharge of refrigerant is reduced by 99 %. No twist, no turn, no hand-tightening. Just push to connect.
Description
WEH® Connector TW111 for filling refrigerants on Schrader valves - Product family

The WEH® TW111 service connector is the ideal tool for filling refrigerants. Thanks to the easy push & pull actuation, the TW111 connects to Schrader valves in just seconds. The safe and pressure-tight connection is established without continuous screwing and unscrewing of threaded ports. Thus the operator's joints are protected from injuries arising from repetitive motion. Work flows are considerably facilitated and a high operating comfort is achieved.

In addition, the WEH® TW111 filling connector reduces the loss of refrigerant by up to 99%. An integrated shut-off valve allows only a minimum of refrigerant to escape into the air. Besides environmental protection, the operator is protected from cold burns to the hands.

Connection times are reduced, costs are cut and the productivity is increased.

The TW111 is optionally available with central or 90° media inlet. The colour-coded sliding sleeve, red or blue, for the high pressure respectively low pressure test piece port avoids mistaken use. The service connector is rated for an operating pressure of max. 42 bar and is equipped with a chloroprene front seal as standard. Versions with EPDM front seal for filling the refrigerant R410A are available. Other sealing materials on request. It is the customer’s responsibility to clarify the media compatibility.

TW111 is also available in convenient Pro Sets. These are available either with in-line or 90° media inlets and consist of one connector for the high pressure side, one adapter for the low pressure side, a front seal seat and an O-ring picker.

Features
  • For connection to Schrader valves
  • No frostbitten or burned hands
  • 99 % less refrigerant loss
  • Connection in seconds
  • No hand tightening required
  • WEH® Jaw Locking Mechanism
  • Reduces connection times and costs
  • Different versions available
  • High-grade materials
Technical Data
Max. allowable operating pressure PS 42 bar (610 psi)
Temperature range -10 °C up to +80 °C
Actuation Manual actuation via sliding sleeve
Design With integrated shut-off valve
Material Brass and anodized aluminium
Sealing material Front seal of chloroprene resp. EPDM (R410A)
Application
Quick connector for filling and evacuating refrigerants of industrial refrigerating and air conditioning systems with Schrader valve acc. to SAE J513.
Downloads
Document type Format Size Download
Datasheet PDF 306 KB
Quick Facts PDF 203 KB
Product Family
The TW111 Series for filling refrigerants up to max. 42 bar is available in different versions. Other connections and sizes on request.
Inquiry List

 

You have no items in your inquiry list.

Read more

Service quick coupling for filling refrigerants with Schrader valves - WEH® TW111

The service quick coupler TW111 is the ideal service port access fitting for charging and recharging refrigerants and air conditioning plants with Schrader valves. The service coupler connects instantly to your external threaded service port of RAC systems / ACR systems. The TW111 offers quick connect and quick disconnect thanks to the WEH® Jaw Locking Mechanism and the easy to operate sliding sleeve. The service quick coupler also eliminates hazardous discharge of refrigerant from high-side / low-side of system when disconnecting. Applications are recharging of home air conditioners and refrigerators.

Back to Top